1STABLE AND RELIABLE OPERATE AT -25℃

Under low ambient temperatures, the performance, heating ability, and operational stability of normal heat pumps will be limited. Power World's R290 full DC inverter heat pump can operate stably and efficiently in extremely cold regions of -25°C without EVI technology, maintaining a high COP and outputting 75°C hot water to ensure the heating and cooling of the house need.

R290

 

 

Specification:

Model PW030-DKZLRS-E/S PW040-DKZLRS-E/S PW050-DKZLRS-E/S PW050-DKZLRS-E PW060-DKZLRS-E
Heating Condition - Ambient Temp. (DB/WB): 7/6℃, Water Temp. (In/Out):30/35℃
Heating Capacity Range (kW) 3.3~8.3 4.5~11.4 5.9~14.8 5.9~14.8 8.8~22.0
Heating Power Input Range(kW) 0.64~2.18 0.85~2.95 1.13~3.83 1.13~3.83 1.68~5.77
COP Range 3.81~5.17 3.86~5.29 3.86~5.22 3.86~5.22 3.81~5.24
DHW Condition-Ambient Temp. (DB/WB): 7/6℃, Water Temp. (In/Out):15/55℃
Heating Capacity Range (kW) 3.7~7.4 5.2~10.2 6.6~13.2 6.6~13.2 7.8~17.6
Heating Power Input Range(kW) 0.79~2.10 1.10~2.87 1.41~3.73 1.41~3.73 1.67~5.01
COP Range 3.52~4.69 3.55~4.71 3.54~4.67 3.54~4.67 3.51~4.66
Heated water output (L/H) 159 219 283 283 377
Cooling Condition - Ambient Temp. (DB/WB):35/24℃,Water Temp.(In/Out):12/7℃
Cooling Capacity Range (kW) 2.4~5.8 3.3~8.2 4.3~10.8 4.3~10.8 6.2~15.3
Cooling Power Input Range(kW) 0.79~2.19 1.08~3.07 1.39~3.99 1.39~3.99 1.99~5.60
EER Range 2.65~3.04 2.67~3.06 2.71~3.10 2.71~3.10 2.73~3.12
Space
Heating
(According to
EN14825:2022)
Average Climate Water Outlet 35°C
Rated heat output (kW) 6.0 8.0 10.0 10.0 14.0
Seasonal Space Heating Energy Efficiency (SCOP) 4.64 4.70 4.65 4.60 4.69
ErP Level A+++ A+++ A+++ A+++ A+++
Sound pressure level (dB(A)) at 1 meter 44 43 45 44 45
Space
Heating
(According to
EN14825:2022)
Average Climate Water Outlet 55°C
Rated heat output (kW) 6.0 9.0 9.0 12.0 13.0
Seasonal Space Heating Energy Efficiency (SCOP) 3.48 3.66 3.37 3.44 3.55
ErP Level A++ A++ A++ A++ A++
Sound pressure level (dB(A)) at 1 meter 44 47 46 45 46
Power supply 230V/1Ph/50Hz/60Hz 380V/3Ph/50-60Hz
Diameter of pipe (mm) DN25 DN25 DN25 DN25 DN25
Max water head(m) 9 9 9 9 12
Net Weight (kg) 112 120 138 138 170
Body size(W*D*H) (mm) 1080×460×820 1080×460×960 1080×480×1060 1080×480×1060 1080×480×1372
Operation Ambient Temp. (℃) -25~43℃
Operating water temperature (℃) 20~65℃(DHW)
Operating water temperature (℃) 20~70℃(Heating)
Operating water temperature (℃) 7~35℃(Cooling)